Ventilation · UK · Guide
MVHR explained: when heat recovery ventilation makes sense
Seal a house tight enough to keep the heat in and you also keep the stale air in. Explained in one line, MVHR is the fix for that problem, and in the wrong house it is an expensive answer to a question nobody asked.
Key facts
- The 2026 edition of Approved Document F takes effect in England on 24 March 2027 for most building work.1
- Natural ventilation is guidance only for less airtight homes; MVHR and continuous extract cover any home, however airtight.1
- A three-bedroom home needs at least 31 litres a second of whole-house ventilation, or 0.3 l/s per m² of floor area if that is higher.1
- In a new home, the air flow rates of mechanical ventilation must be measured and reported to building control.1
On this page
Close the windows in a well-insulated new home on a January evening and something odd happens. The house stays warm, the boiler or heat pump barely ticks over, and by morning the bathroom mirror is fogged, the bedroom air is stale and there is a damp patch behind the wardrobe. Airtightness keeps the heat in. It keeps everything else in too.
Mechanical ventilation with heat recovery, MVHR for short, is the engineered answer. A fan unit, usually in a loft or cupboard, draws stale air out of the kitchen and bathrooms and pushes fresh, filtered air into the living rooms and bedrooms. On the way, the two airstreams pass each other inside a heat exchanger, so the warmth in the outgoing air goes to the incoming air instead of out of the building.
Our verdict, up front: MVHR earns its place in a new build or a deep retrofit that has been properly sealed. In an older, draughty house with a condensation problem, it is usually the wrong first move, and a simpler system will do the job for far less disruption.
What MVHR means, in plain terms
The name spells out the three parts. Mechanical ventilation: fans move the air, not open windows or trickle vents. Heat recovery: a heat exchanger warms the incoming air with the outgoing air. System: ducts connect every room, so it is a whole-house installation, not a fan you screw to a wall.
The rules for how it is laid out are specific. Each habitable room gets its own mechanical supply of fresh air, and the total supply is shared out in proportion to the volume of each room.1 Supply grilles have to be placed and aimed so they don’t cause draughts.1 And because the system relies on a sealed building, trickle vents in the windows should not be fitted alongside it: they create unplanned air paths.1
That last point tells you most of what you need to know. MVHR works best in a home that leaks very little air. The more airtight the house, the more of the heat the system can actually recover.1
Which homes the 2026 rules point towards MVHR
Approved Document F is the government guidance on ventilation in England. Earlier editions keep applying to buildings that fall under the previous rules.2 A new 2026 edition takes effect on 24 March 2027 for most building work, and on 24 September 2027 for work on higher-risk buildings.1 It arrives with the Future Homes and Buildings Standards, which require new homes to have low-carbon heating and on-site renewable electricity.3 Projects that gave notice before 24 March 2027 and start work before 24 March 2028 can still build to the old rules.3
The new document gives guidance for three types of system, and each one comes with a limit on where it applies:1
| System | Homes the guidance covers |
|---|---|
| Natural ventilation with trickle vents and intermittent extract fans | Less airtight homes only1 |
| Continuous mechanical extract ventilation | Any home, however airtight1 |
| Mechanical ventilation with heat recovery | Any home, however airtight1 |
If a home was designed for natural ventilation but turns out tighter than planned when it is tested, the builder must either take expert advice or fit continuous mechanical extract.1 So in a highly airtight new home, the realistic choice is between continuous extract and MVHR. Extract alone throws the warm air away; MVHR keeps most of the heat. That is why it pairs naturally with a heat pump in a well-sealed house.
How much air does a home need?
The guidance sets a minimum whole-house rate for fresh air supplied to the living rooms and bedrooms. A home must meet both of two tests: at least 0.3 litres per second for every square metre of internal floor area, counting every storey, and at least the rate for its number of bedrooms.1
Add 6 l/s for each bedroom beyond five.1 For an MVHR system, this whole-house rate is the minimum it must run at continuously.1 Take a three-bedroom house with 120 m² of floor space: the floor-area test gives 36 l/s, which beats the 31 l/s bedroom figure, so 36 l/s is the target.1
Those are the numbers your designer works to. You don’t need to calculate them yourself, but asking for them is a quick way to see whether a quote has been designed for your house or copied from the last one.
MVHR or PIV for an existing home?
Positive input ventilation, PIV, is the system most often sold for condensation in existing houses. A single unit sits in the loft and pushes air down into the house through a ceiling diffuser. Nuaire’s Drimaster-Eco is a common example. Its loft version adjusts the air volume to the loft temperature, there is a version with its controls in the hall ceiling diffuser instead, and the separate Flatmaster range is made for homes with no loft.4 Warranties run to five years on the loft-controlled unit and seven on the hall-controlled one, with only the first year covering labour.4
PIV is not one of the three system types the new Approved Document F gives guidance for, so it is a retrofit fix rather than a way to meet the rules in a new home.1 For an older home with damp on the bedroom walls, that hardly matters. It is one unit and one hole in the ceiling, where MVHR means ducts to every room.
The rules for existing homes are worth knowing either way. When you replace windows or do energy-efficiency work, the ventilation afterwards must either meet the current standard or be no worse than before.1 If the work cuts ventilation enough, MVHR is one of the listed ways to restore it, with the old trickle vents covered or sealed.1 That is the case for MVHR in a retrofit: a whole-house upgrade with new windows, insulation and serious draught-proofing, done at the same time.
Two MVHR units compared
Zehnder ComfoAir Q
A sound unit, sized by floor area, with a modulating summer bypass for hot days.
- Heat recovery
- 96%
- Sizes or capacity
- Q350 ST up to 250 m², Q450 ST up to 300 m², Q600 ST up to 350 m²
- Filters
- G4 and F7 (F7 for Passivhaus)
- Summer bypass
- Modulating summer bypass
Vent-Axia Lo-Carbon Sentinel Kinetic Plus B
A sound unit whose humidity sensor speeds the fans up, with a night-time setback.
- Heat recovery
- almost 90%
- Sizes or capacity
- 400 m³/h at 150 Pa; extracts from up to ten bathrooms and a communal kitchen
- Filters
- G3 standard; ISO ePM10 50% (M5) pollen filter as an accessory
- Summer bypass
- –
| Zehnder ComfoAir Q | Vent-Axia Lo-Carbon Sentinel Kinetic Plus B | |
|---|---|---|
| Heat recovery | 96%5 | almost 90%6 |
| Sizes or capacity | Q350 ST up to 250 m², Q450 ST up to 300 m², Q600 ST up to 350 m²5 | 400 m³/h at 150 Pa; extracts from up to ten bathrooms and a communal kitchen6 |
| Filters | G4 and F7 (F7 for Passivhaus)5 | G3 standard; ISO ePM10 50% (M5) pollen filter as an accessory6 |
| Summer bypass | Modulating summer bypass5 | – |
| Controls | On-unit display, optional CO2 sensors, installer portal5 | Integrated digital controller, built-in humidity sensor with night-time setback6 |
| Other | Passive House certified; SFP as low as 0.53 (Q450)5 | IP22; 125 mm duct connections6 |
Each cell cites its source.
Heat-recovery percentages are the headline everyone quotes, and here they differ by several points. More useful in practice: the Zehnder is sized by floor area and has a modulating summer bypass, so it can stop warming the incoming air on hot days.5 The Vent-Axia has a built-in humidity sensor that speeds the fans up as humidity rises, with a night-time setting that stops it boosting needlessly while you sleep.6 Either is a sound unit. Choose the installer first; a poorly designed duct run spoils any unit.
MVHR and a heat pump
The two are a natural pair in a new home. The Future Homes and Buildings Standards require low-carbon heating in new homes from 24 March 2027, and a highly airtight home needs mechanical ventilation.3,1 A heat pump runs most cheaply at a low flow temperature, which is easiest to achieve in a house that keeps its heat. MVHR lets you seal the house without losing the warmth in the stale air. Our explainer on how a heat pump works shows why flow temperature matters so much.
One figure to ask about is specific fan power, SFP: how much electricity the fans use for the air they move. Lower is better. The Zehnder ComfoAir Q450 quotes an SFP as low as 0.53.5 Ask for the figure at your home’s design air flow, not the best case.
Filters, servicing and access
An MVHR system is only as good as its filters. You should have reasonable access to replace filters, fans and coils, and to maintain the ductwork.1 Before you sign off the design, check where the unit will sit and whether you can actually reach it. A unit wedged behind boarded-over loft insulation will not get its filters changed.
The Zehnder takes G4 and F7 filters; the Vent-Axia comes with a standard G3 filter, and an M5 pollen filter is an option.5,6 Buy a spare set when the system goes in, and note the change interval the installer gives you.
What you should get at handover
Plenty of installations fall short here, and the rules are firm.
- Commissioning by a competent person. Anyone commissioning a mechanical ventilation system, other than a single intermittent extract fan in an existing home, should belong to a body that regularly checks their competence, such as a competent person scheme.1 The Future Homes circular also points to competent person schemes for mechanical ventilation work.3
- Measured air flows. In a new home, the air flow rates must be measured and a notice of them given to building control.1
- Working controls. The installer should test each control, label it clearly, and check that the summer bypass works as the maker intends.1
- Paperwork you can use. You should receive the design flow rates and maintenance requirements in plain language, plus a copy of the completed commissioning sheet.1
If any of these is missing, ask for it before the final invoice is paid.
Our verdict
- Building new, or gutting and sealing an old house: fit MVHR, sized to the whole-house rate, with the unit somewhere you can service it. Pair it with the low-carbon heating the new standards already require.3
- Existing house with condensation and no wider retrofit planned: start with extract fans that work and consider PIV. MVHR in a leaky house recovers little heat for a lot of ductwork.
- Replacing windows or insulating heavily: plan ventilation at the same time. The rules require it, and MVHR is the option that keeps the heat you just paid to retain.1
Heat pump next? Our guide to air source heat pumps covers sizing and grants, and how a heat pump works explains why a tight, well-ventilated house suits one.
Products compared
Zehnder
Zehnder ComfoAir Q
Passive House certified- Heat recovery
- 96% heat recovery1
Price: No published price
Zehnder ComfoAir Q: Where to buy: zehnder.co.uk
as of · zehnder.co.uk
Vent-Axia
Vent-Axia Lo-Carbon Sentinel Kinetic Plus B
Price: No published price
Vent-Axia Lo-Carbon Sentinel Kinetic Plus B: Where to buy: vent-axia.com
as of · vent-axia.com
Specifications come from each maker's own product page or datasheet, taken on 14 NOV 2026. Our picks are editorial judgement from those published specs, not test results; we haven't tested the products. – means the maker publishes no price.
Rules and grants in force
Future Homes and Buildings Standards (England)
GOV.UK
New homes in England will need low-carbon heating and on-site renewable electricity, and a new Approved Document F sets the ventilation rules. The standards apply from 24 March 2027 (24 September 2027 for higher-risk buildings). Projects that give notice before 24 March 2027 and start work before 24 March 2028 can follow the old rules.
Official source gov.uk
Updated · against gov.uk
Dated rule changes
-
in 126 days
Future Homes and Buildings Standards apply in England
New homes need low-carbon heating and on-site renewable electricity, with new ventilation rules in Approved Document F. Higher-risk buildings follow on 24 September 2027.